Reading your electricity bill: the numbers that matter for solar

Which lines solar can reduce, which it cannot, and how to find your real avoidable cost per unit.

Short answer

Rooftop solar reduces the per-unit lines on your bill (the energy charge and per-unit additions), not demand or fixed charges. The number to find is your avoidable cost per unit: the per-unit charges only, which is usually lower than the total bill divided by units. Use that figure, not the average, to judge any proposal.

Key takeaways

  • Rooftop solar reduces the per-unit lines on your bill. It rarely reduces demand or fixed charges.
  • Each solar unit saves your avoidable cost per unit, which is usually lower than your average rate. Work it out before you read any proposal.
  • Time-of-day tariffs matter: units replaced during solar hours may be priced lower than your normal rate.
  • Contract demand, voltage and tariff category decide which options are open to you, including green open access from 100 kW.

Start with 12 months of bills

One bill shows a month. Twelve show the pattern: monsoon dips, production peaks, tariff revisions and penalties that keep coming back. Most of what a solar proposal assumes about your factory can be checked against them. Pull a full year for each connection before you speak to any vendor. If your meter records time-of-day or 15-minute interval data, ask your DISCOM or meter provider for that too.

Six lines to read first on a factory bill

Tariff category and supply voltage

HT or LT (high-tension or low-tension supply), industrial or commercial, and the voltage you take supply at. Together they decide which tariff schedule applies to you, which metering arrangements are allowed and whether open access is an option.

Contract demand and recorded maximum demand

Contract demand (in kVA or kW) is the load you have agreed with the DISCOM. Recorded maximum demand is the highest reading in the billing period. Demand charges are billed on the higher of the recorded figure and a minimum set by your tariff, often a share of contract demand. Contract demand also caps how large a grid-connected plant some states allow.

Units consumed, in kWh or kVAh

Monthly consumption tells you how much solar you can use. Check the billing unit as well: some tariffs bill apparent energy (kVAh) rather than active energy (kWh), which changes how power factor affects the bill.

Energy charge and other per-unit charges

The energy charge per unit, plus any per-unit additions: fuel or power-purchase adjustment charges, and duties or taxes levied on consumption. These are the lines a solar unit replaces.

Time-of-day split

A time-of-day (ToD) tariff prices power by the hour of use. Under the Electricity (Rights of Consumers) Amendment Rules, 2023, commercial and industrial consumers with maximum demand above 10 kW were to move to time-of-day tariffs by 1 April 2024. The rules set the peak-hour tariff at not less than 1.2 times the normal tariff for these consumers and a lower tariff for solar hours, applied to the energy charge. Your bill’s split across slots shows what each solar unit is worth.

Power factor

Look for power factor penalties or incentives. A solar plant changes the mix of active and reactive power drawn from the grid, so this line can move after commissioning.

Why the average rate overstates what solar saves

The quick way to read a bill is to divide the total by the units. That average includes demand and fixed charges that solar will not touch, so it overstates what each solar unit saves.

Illustrative exampleOne month on an HT industrial bill

Assumptions

  • 7,00,000 units consumed; total bill ₹62 lakh
  • Demand charges ₹9 lakh; other fixed charges ₹1 lakh
Average rate (total ÷ units)
₹8.86 per unit
Avoidable rate (per-unit charges only)
₹7.43 per unit
Saving overstated on 1,00,000 solar units by using the average
₹1.43 lakh

The avoidable rate, ₹7.43, is the figure to use. With time-of-day pricing, refine it further by weighting each slot by the solar units it receives.

Assumed figures to show the method. Not a quote and not a result from any Adhvanik plant.

Which bill lines rooftop solar reduces

General guide. Tariff structures differ by state and category; your tariff order is the final word.
Bill lineReduced by rooftop solar?Why
Energy chargeYesEvery unit consumed from the plant is a unit not bought from the DISCOM.
Per-unit adjustment chargesUsuallyWhere levied per unit consumed, they fall with grid units.
Duties and taxesDepends on the stateSome states also levy duty or tax on self-generated units.
Demand chargesRarelyMaximum demand can be set by a moment of cloud; storage or load shifting lowers it reliably.
Fixed chargesNoThey depend on your connection, not your consumption.
Power factor penalty or incentiveIt can move either wayPlan inverter settings and capacitor banks with the design.

When the roof cannot cover your load

If your daytime consumption is far larger than your roof can serve, look at open access: power generated elsewhere and supplied to your factory over the grid. The Green Energy Open Access Rules, 2022 brought the open access threshold for green power down to 100 kW, and a later amendment allows that to be met by adding up connections in the same electricity division. States apply these rules through their own regulations, so eligibility and charges still need checking for yours. Rooftop and ground-mount solar inside your boundary come first, because they avoid wheeling charges and open-access surcharges. A few states levy network or grid-support charges on rooftop generation, so check yours.

Four questions to put to any vendor about your bill

  1. Which lines of my bill does your saving figure assume solar will reduce?

    If demand or fixed charges are in the saving, the proposal is overstated.

  2. Have you used my time-of-day split, or a flat tariff?

    Solar-hour units may be cheaper than your normal rate, so a flat tariff can overstate savings.

  3. How will the plant affect my power factor, and who handles compensation?

    A new penalty can eat into the saving if nobody plans for it.

  4. Is the plant size within what my contract demand and state rules allow?

    An oversized design can stall at DISCOM approval.

Send us your last 12 bills and an engineer gets back to you within 48 hours with what your roof can save. For plants that need storage to bring down demand charges, see battery energy storage.

Sources

Policy and tax rules change. Facts below were checked in Nov 2026; confirm the version in force for your state and tax year before you sign.

  1. Electricity (Rights of Consumers) Amendment Rules, 2023: rule 8A, Time of Day tariff (opens in a new tab)
  2. PIB (Ministry of Power): Green Energy Open Access Rules, 2022 (opens in a new tab)
  3. Mercom: consumers with aggregate demand of 100 kW can avail green energy open access (opens in a new tab)
  4. Mercom: Tamil Nadu cuts rooftop solar network charges (opens in a new tab). an example of a state charge on rooftop generation

Common questions

Demand charges, power factor and kVAh

Short answers. The working is in the guide above.

Get a free feasibility study
Will solar reduce our maximum demand charges?

Rarely on its own. Billing demand is set by your highest reading in the month, and a passing cloud at that moment means the solar plant contributes little. Battery storage, or shifting load, is what reliably lowers a peak.

Do we need bills for all our meters?

For every connection the plant could feed. If the factory has several connections, the plant normally serves one of them, and its bill is the one that matters most.

Why does our power factor change after solar?

The plant supplies active power, so the grid supplies less of it but the same reactive power, and the power factor measured at the grid meter falls. Inverter settings and your capacitor banks can compensate; ask how the design handles it.

Our bill shows kVAh, not kWh. Does that matter?

Yes. Under kVAh billing, a lower power factor at the grid meter raises the billed energy. The saving model should account for it.

Free feasibility study

Have an engineer read your bill for solar

The feasibility study is free, takes 7 days and carries no commitment. An engineer replies within 48 hours.

What the study covers

  • Financial ROI sheet based on a preliminary design
  • Policy check for your state and connection
  • Roof feasibility and the area available for installation
Call us+91 22 4618 3484Get a free feasibility study