Why PR beats units generated
Generation rises and falls with the weather, so a poor month may have been a cloudy one. PR takes sunshine out of the comparison. It tells you how much of the available energy the plant turned into usable power, which lets you compare one month with another, one year with the next, and one plant with another.
How PR is calculated
IEC 61724-1, the international standard for PV monitoring, defines PR as the plant's final yield divided by its reference yield.
- Final yield (Yf) is the AC energy the plant delivered, in kWh, divided by its DC capacity in kWp (see kWp vs kW).
- Reference yield (Yr) is the solar irradiation measured in the plane of the modules, in kWh/m², divided by the reference irradiance of 1 kW/m². It equals the number of hours the plant would have run at full sun.
A plant with no losses at all would score 100%. Real plants lose energy to heat, wiring, inverters and dirt, so PR is lower.
What drags PR down
Dust and bird droppings on modules, shading from new structures, failed strings or bypass diodes, inverter faults and trips, loose connections, and grid outages all lower PR. High module temperature does too, which is why some contracts use a temperature-corrected PR. A falling PR is often the first sign of a fault that the generation figure alone would hide.
Illustrative example
Worked example: one month of PR
A 500 kWp plant over one month.
- Irradiation in the plane of the modules
- 160 kWh/m², so reference yield = 160 hours
- Energy delivered
- 62,400 kWh
- Final yield
- 62,400 ÷ 500 = 124.8 kWh/kWp
PR = 124.8 ÷ 160 = 78%.
Illustrative numbers. Your plant's PR comes from its own meter and sensor data.
What to check in a PR guarantee
- Which irradiance sensor is used, where it is mounted, and how often it is calibrated
- Whether PR is temperature-corrected or not
- What is excluded: grid outages, curtailment, your own shutdowns
- Whether energy is measured at the inverter or at the export meter
- Whether PR is tested monthly or annually, and how a shortfall is paid
PR on the plants we maintain
We offer a 95% uptime guarantee, plus a performance-ratio guarantee. Lost generation is credited at ₹3.00/kWh. On the plants we maintain, generation has typically run 3–7% above guaranteed yield. PR, irradiance and generation are tracked on Asset Connect, our monitoring platform.