Plant performance

Performance ratio (PR)

Performance ratio (PR) is the share of the energy a solar plant could have produced, given the sunlight that fell on it, that it delivered; it is the standard measure of how well a plant is run.

Why PR beats units generated

Generation rises and falls with the weather, so a poor month may have been a cloudy one. PR takes sunshine out of the comparison. It tells you how much of the available energy the plant turned into usable power, which lets you compare one month with another, one year with the next, and one plant with another.

How PR is calculated

IEC 61724-1, the international standard for PV monitoring, defines PR as the plant's final yield divided by its reference yield.

  • Final yield (Yf) is the AC energy the plant delivered, in kWh, divided by its DC capacity in kWp (see kWp vs kW).
  • Reference yield (Yr) is the solar irradiation measured in the plane of the modules, in kWh/m², divided by the reference irradiance of 1 kW/m². It equals the number of hours the plant would have run at full sun.

A plant with no losses at all would score 100%. Real plants lose energy to heat, wiring, inverters and dirt, so PR is lower.

What drags PR down

Dust and bird droppings on modules, shading from new structures, failed strings or bypass diodes, inverter faults and trips, loose connections, and grid outages all lower PR. High module temperature does too, which is why some contracts use a temperature-corrected PR. A falling PR is often the first sign of a fault that the generation figure alone would hide.

Illustrative example

Worked example: one month of PR

A 500 kWp plant over one month.

Irradiation in the plane of the modules
160 kWh/m², so reference yield = 160 hours
Energy delivered
62,400 kWh
Final yield
62,400 ÷ 500 = 124.8 kWh/kWp

PR = 124.8 ÷ 160 = 78%.

Illustrative numbers. Your plant's PR comes from its own meter and sensor data.

What to check in a PR guarantee

  • Which irradiance sensor is used, where it is mounted, and how often it is calibrated
  • Whether PR is temperature-corrected or not
  • What is excluded: grid outages, curtailment, your own shutdowns
  • Whether energy is measured at the inverter or at the export meter
  • Whether PR is tested monthly or annually, and how a shortfall is paid

PR on the plants we maintain

We offer a 95% uptime guarantee, plus a performance-ratio guarantee. Lost generation is credited at ₹3.00/kWh. On the plants we maintain, generation has typically run 3–7% above guaranteed yield. PR, irradiance and generation are tracked on Asset Connect, our monitoring platform.

See our O&M guarantees

Sources

  1. Hukseflux: how to calculate PV performance ratio under IEC 61724-1 (opens in a new tab)

Related terms

  • Plant performance

    CUF

    Capacity utilisation factor: the energy a plant produced in a period divided by what it would have produced running at full rated capacity every hour of that period.

  • Plant performance

    Specific yield

    Energy generated per unit of installed capacity, in kWh per kWp per year. It depends mainly on location, tilt and shading, and lets you compare plants of different sizes.

  • Plant performance

    Degradation

    The gradual loss of a module's output over the years. Module warranties state the maximum loss allowed in the first year and in each year after.

  • Equipment & O&M

    SCADA

    Supervisory control and data acquisition: the system that collects live data from inverters, meters and sensors so engineers can monitor a plant and act on faults remotely.

Keep reading

Free feasibility study

Ask about PR guarantees for your plant

The feasibility study is free, takes 7 days and carries no commitment. An engineer replies within 48 hours.

What the study covers

  • Financial ROI sheet based on a preliminary design
  • Policy check for your state and connection
  • Roof feasibility and the area available for installation
Call us+91 22 4618 3484Get a free feasibility study