What CUF tells you
CUF answers a simple question: for each kilowatt of capacity, how much energy did the plant deliver over the year? Because a solar plant produces nothing at night and little on cloudy days, its CUF is far below 100%. It is a useful way to compare plants at different locations or to sense-check a generation estimate.
AC or DC: say which
CUF can be calculated on the plant's DC capacity (kWp of modules) or its AC capacity (kW of inverters). When the DC/AC ratio is above 1, which is normal, CUF on an AC basis is higher than on a DC basis for the same plant. Two proposals quoting CUF on different bases can look different while promising the same output.
CUF, PR and specific yield
- CUF measures output against round-the-clock capacity. It moves with the weather and the location.
- Specific yield is the same information in kWh per kWp per year.
- Performance ratio measures output against the sunlight that arrived, so it shows how well the plant is being run.
Utility-scale tenders in India commonly fix a declared CUF the developer must meet. For a factory rooftop plant, a generation or PR guarantee is usually the more useful contract measure.
Illustrative example
Worked example: one plant, two CUFs
A plant with 1,000 kWp of modules and 800 kW of inverters generates 13,00,000 kWh in a year.
- CUF on DC capacity
- 13,00,000 ÷ (1,000 × 8,760) = 14.8%
- CUF on AC capacity
- 13,00,000 ÷ (800 × 8,760) = 18.6%
- Specific yield
- 13,00,000 ÷ 1,000 = 1,300 kWh/kWp
Same plant, same year: the basis changes the number.
Illustrative numbers.
When a proposal quotes CUF
- Is it on AC or DC capacity?
- Is generation measured at the inverter or at the export meter?
- Which weather data was used, and for which year?
- Is it a guaranteed figure or an estimate?